1. The main functions of the lightning arrester intelligent monitoring meter are:
Automatic monitoring function
Periodic automatic monitoring of the full current, number of actions, and action time of the lightning arrester.
Data storage function
It has the function of saving and exporting historical data, and can automatically store 10000 monitoring data periodically.
communication function
Equipped with RS485 data upload function, meeting the MODBUS protocol.
alarm function
Equipped with abnormal alarm function, real-time alarm will be triggered when monitoring data exceeds the standard, monitoring function fails, communication interruption and other abnormalities occur. The alarm settings can be modified, and the alarm information can be transmitted remotely in real time.
Local display function
The lightning arrester action count is displayed using a 3-digit electromagnetic counter. The full current is displayed on a scale. The scale has a normal area (green), a caution area (yellow), and an alarm area (red).
Scale indication | |||
serial number |
Full current range |
status display |
status judgment |
one |
0.5-2.5mA |
green |
normal |
two |
2.5-3.5mA |
yellow |
Attention |
three |
3.5-5mA |
red |
call the police |
Table 1
Meter appearance
The device adopts a meter style appearance structure, which is consistent with the installation size of traditional lightning arrester monitors and can be directly replaced for installation.